Salisbury Renal Unit

Overall: Good read more about inspection ratings

Block 8, 10 Odstock Road, Salisbury, SP2 8BJ (01722) 677020

Provided and run by:
Diaverum UK Limited

Important: The provider of this service changed. See old profile

Assessment report published 13 November 2026

On this page

Safe

Good

13 November 2026

This means we looked for evidence that people were protected from abuse and avoidable harm. This is the first rated assessment for Salisbury Renal Unit. This key question has been rated as good. This meant people were safe and protected from avoidable harm.

We have not awarded this service a score for Safe.

Find out about when we will not publish a key question score and what we look at when we assess Safe.

Learning culture

Score: 3

The service had a positive learning culture. Staff reported incidents, near misses, and patient safety concerns through the provider's reporting systems and the partner acute trust's system. Leaders investigated incidents, identified causes, developed action plans, and shared learning with staff. They also reviewed policies, updated procedures, and provided additional training where required. This supported continuous improvement and patient safety.

The service had clear processes for learning from incidents. Leaders used a risk assessment framework to decide the level of investigation required and completed root cause analyses for significant incidents. Staff told us they received feedback following incidents and near misses and understood the importance of reporting concerns. Staff were aware of duty of candour requirements and described an open culture where learning was valued. This helped prevent incidents reoccurring.

Leaders promoted openness and transparency when things went wrong. Policies required staff to communicate honestly with patients and families, investigate incidents thoroughly, and share learning. We reviewed 3 serious incident investigations and found evidence that leaders identified learning and took action to improve practice. For example, following a documentation incident, leaders reinforced record-keeping standards and provided additional training on maintaining accurate records and audit trails.

Learning from incidents led to changes in practice. Staff described how an incident at another clinic resulted in only registered nurses being permitted to prime dialysis machines. Learning from needlestick injuries was also shared across clinics to reinforce safe working practices. An audit identified concerns about the availability of sharps bins during treatment, and leaders were introducing trolley-mounted sharps bins to reduce risk. Staff also followed a standardised process for securing dialysis needles and bloodlines to reduce the risk of dislodgement and treatment interruption.

Staff had regular opportunities to learn and develop. Weekly ‘Nursing Nuggets’ sessions covered topics such as dementia awareness, diabetic foot checks, pressure ulcer prevention, and health and safety. Staff discussed incidents during daily huddles, learning was shared through emails and team meetings, and action plans were displayed within the unit. Staff told us they were supported to complete training and additional learning activities. This helped maintain staff knowledge, competence, and confidence.

The service demonstrated an established reporting culture. Between February and August 2026, staff reported 123 incidents, the majority of which were graded as minor or insignificant. Common themes included patient choice, vascular access complications, transport issues, treatment interruptions, and episodes of patient deterioration. Staff told us they would always report incidents and near misses. This gave leaders oversight of risks and supported ongoing learning and improvement.

Safe systems, pathways and transitions

Score: 3

The service had clear systems and pathways to ensure patients received dialysis in the most suitable setting and were transferred safely when their needs changed. Staff followed an admission criterion which helped ensure only patients whose needs could be safely met within the satellite unit received treatment there. Before treatment started, staff reviewed referrals, confirmed patients were clinically stable, had suitable vascular access, and had completed the required screening and assessments. Staff also reviewed infection risks, oxygen requirements, medicines, and resuscitation decisions. More complex referrals were escalated to senior clinical staff and consultants for review. This reduced the risk of patients receiving care in an unsuitable environment and supported safe, person-centred care.

The service supported effective communication and continuity of care between teams. Staff used electronic patient records to document each dialysis session, including patient weights, observations, and clinical information. Consultants could access these records remotely to monitor patients and support decision-making. Staff also maintained regular communication with the wider renal team. They updated the visiting renal consultant during weekly visits and informed renal doctors at their partner trust of any deterioration or changes in a patient's condition. This ensured relevant clinical information was shared promptly and supported coordinated care across services.

The service had effective processes for recognising and responding to deteriorating patients. Staff assessed patients who became unwell before treatment, checked observations, sought medical advice, and escalated concerns to the renal team when required. Policies set out clear criteria for when patients were no longer suitable for treatment within the satellite setting, including where vascular access problems could not be managed on site or where patients required a higher level of medical support. Staff arranged transfer to acute services when necessary and shared relevant information to support ongoing care. This helped ensure patients received timely treatment in the most suitable setting.

The service had emergency pathways for patients who became seriously unwell during dialysis treatment. Staff were trained to respond to medical emergencies and followed established procedures for escalation, resuscitation, and emergency transfer. Guidance was available to support a consistent response to patients who became unresponsive or acutely unwell. This enabled staff to act quickly and reduced the risk of delays in accessing emergency care.

The service had arrangements to support the safe transfer of patients who needed specialist renal care. The transfer policy clearly set out referral processes, transport arrangements and clinical responsibilities between the dialysis service and the partner NHS trust. Staff followed defined pathways for urgent transfers, including patients who required emergency dialysis, specialist vascular access procedures or other urgent renal treatments. Clinicians discussed complex cases with specialist teams and obtained agreement from the receiving consultant before transfer. This helped ensure patients received timely specialist care and that risks were managed safely during transfers between services.

Safeguarding

Score: 3

The service had systems and processes to protect adults at risk from abuse and neglect. Staff understood their safeguarding responsibilities and knew how to recognise, raise and report concerns. The service had a safeguarding adult’s policy that reflected the Care Act 2014, and provided guidance for staff on recognising, reporting and responding to concerns about abuse, harm or neglect. The policy outlined staff responsibilities and the actions to take if concerns were identified.

We observed a vulnerable adult emergency contact poster was displayed in the waiting area to provide information and support patients and visitors. The service had a safeguarding lead. Staff we spoke with understood what safeguarding meant, described it as taking a holistic approach to protecting patients, and knew who to contact for advice and support. Staff told us they had received safeguarding training and felt confident raising concerns when required.

Training records showed safeguarding adults’ level 1 and 2 compliance was 100%, and safeguarding children’s level 1 and 2 compliance was also 100%. In addition, 5 senior staff members completed safeguarding adults’ level 3 training. In line with the Intercollegiate Adult Safeguarding Framework, registered nurses working in dialysis services would normally be expected to demonstrate adult safeguarding level 2 competencies appropriate to their role in providing direct clinical care to adults and recognising, responding to and escalating safeguarding concerns. Staff demonstrated they acted on safeguarding concerns. For example, staff identified concerns about a patient’s wellbeing and raised a safeguarding referral to help ensure the person receives support and protection. Staff told us they documented safeguarding referrals on the provider’s reporting system and informed their partner trust to ensure oversight. This meant staff had the knowledge, training and support needed to identify and respond to safeguarding concerns. 

Involving people to manage risks

Score: 3

The service involved patients in managing risks associated with their care and had systems to identify deterioration early. Staff followed a deteriorating patient policy and used the National Early Warning Score (NEWS2) to assess and monitor patients. They completed observations at the start of each dialysis session and monitored patients hourly throughout treatment. Staff told us NEWS2 helped them identify trends and recognise deterioration promptly, supporting timely intervention.

Staff worked with patients to monitor their health and identify potential risks during treatment. They discussed patients' wellbeing, completed routine observations, and carried out blood glucose monitoring before and after dialysis for patients with diabetes. Staff also checked patients' identity by confirming their name and date of birth before treatment. These processes helped ensure patients received the correct treatment and that concerns were identified promptly.

Staff demonstrated a good understanding of sepsis recognition and the management of deteriorating patients. They escalated concerns and could administer fluids under a patient-specific direction for low blood pressure. A patient specific direction is written instruction which allows nurses to administer a specific medicine to treat a specific problem. The unit had immediate access to emergency support through the on-site hospital, including the resuscitation team, emergency 2222 response, and an on-call medical registrar. This ensured patients could access urgent assessment and treatment without delay.

Compliance with NEWS2 completion was not routinely audited at the time of inspection, and the service could not provide assurance it was being completed consistently across the unit. However, staff demonstrated a good understanding of its use and were able to describe escalation processes for deteriorating patients. Although leaders planned to participate in future trust-led audits, we found no evidence of patient harm relating to NEWS2 completion. Given the outpatient nature of the service, the level of risk was reduced.

Safe environments

Score: 2

Fire safety arrangements required improvement to ensure staff were fully prepared to evacuate patients who needed assistance in an emergency. Although all staff were identified as fire wardens, only one member of staff had completed formal evacuation chair training at the time of inspection. An evacuation chair enables people with reduced mobility to be evacuated safely downstairs when lifts cannot be used. This was particularly important because some patients required assistance with mobility and one of the designated emergency escape routes included external steps. The fire risk assessment completed in September 2023 identified that evidence of evacuation chair training could not be demonstrated and recommended staff receive training and a fire drill be undertaken to test evacuation procedures.

We sought assurance the service could safely evacuate patients who required assistance in the event of a fire. This was important because only one evacuation chair was available, despite occasions when more than one patient attending the same dialysis session required hoist-assisted transfers. We reviewed patients' Personal Emergency Evacuation Plans (PEEPs), which identified more than one patient receiving treatment during the same session could require use of the evacuation chair during an emergency evacuation. We were concerned the arrangements did not provide sufficient assurance that all patients could be evacuated promptly and safely. This could have resulted in delays evacuating patients with reduced mobility during an emergency.

Following the inspection, the service responded quickly to the concerns identified. The registered manager completed evacuation chair train-the-trainer training that had been arranged prior to the inspection and introduced a staff training programme. The provider subsequently confirmed 10 members of staff had completed evacuation chair training. Staff completed a simulated fire drill, reviewed evacuation routes, identified designated evacuation chair operators and worked with a local trust to test emergency support arrangements. We were further informed an agreement had been arranged for an additional evacuation chair to be provided if required to support the safe evacuation of all patients during a fire. These actions improved assurance that patients could be evacuated safely in the event of a fire.

The patient treatment area was small, which limited the space available for equipment and day-to-day activities. On arrival, we observed 2 metal trolleys in front of the resuscitation trolley. Staff moved these immediately when the issue was raised. We also found the crash trolley positioned between the nurses' station and a dialysis station, which meant staff would need to move a patient and equipment to access it quickly in an emergency. The registered manager addressed this promptly and relocated the trolley to a more accessible location. We observed dialysis stations were positioned close together. During our observations, a tea trolley round briefly paused to allow a medicine round to take place, demonstrating the need to coordinate activities within the available space. We also found 3 spare dialysis machines stored in the water treatment room because of limited storage capacity elsewhere in the unit. Nurses told us 2 dialysis stations were slightly larger than the others and were designated for patients who were bedbound or required hoist transfers, as these stations could accommodate additional equipment and support their care needs. Although staff managed these constraints well and responded to concerns, ongoing oversight was needed to ensure the environment remained safe for patients and staff.

Despite these concerns, we found several systems and controls that supported a safe environment. The service maintained an inventory of dialysis machines, monitored equipment age and servicing requirements, and had ongoing planned preventative maintenance schedules. Most dialysis machines were purchased in June 2020, and all machines had future maintenance dates scheduled between December 2026 and July 2027. Staff carried out function checks of dialysis machines and removed equipment from use when faults were identified pending technician review. The service had 15 dialysis machines available, including 3 spare machines.

Equipment maintenance records demonstrated that equipment remained fit for purpose. Portable appliance testing for electrical equipment had passed in May 2026. Electrical safety testing of 12 therapy chairs passed in June 2026. Medical equipment, including thermometers, blood glucose monitors, suction equipment, passed testing in February 2026. Hoist servicing and stand aid servicing were scheduled for December 2026.

Staff completed and documented regular emergency checks. Resuscitation trolley records showed no gaps in checks between March to August 2026, with only one omission identified in March. Daily and monthly crash trolley checks were completed, emergency consumables and medicines were within expiry dates, and the defibrillator and suction equipment were connected and ready for use. The service stored oxygen cylinders upright on stands to reduce the risk of them falling and causing injury. Staff also maintained a stocked box containing items to treat low blood sugar with in-date medicines.

The provider had arrangements to manage water quality and dialysis safety. A water treatment policy mandated daily, weekly, and monthly checks of the water treatment system. Only trained staff could undertake monitoring, results were documented, and staff told us they would escalate any readings outside acceptable limits. The registered manager told us they reviewed monitoring records regularly. Water treatment monitoring logs for June, July and August 2026 contained no gaps, and all ranges were identified to be within acceptable limits.

Storage arrangements were generally acceptable. We found consumables stored off the floor and checked a sample of items, including syringes, needles, gloves, dressings and masks, which were all in date. The service segregated waste using colour coded bins. Staff securely stored hazardous substances, including citric acid for dialysis, in locked COSHH (Control of Substances Hazardous to Health) cupboards. The external clinical waste compound was locked; fluid storage areas were temperature monitored daily and keycode access restricted entry to clinical areas.

Safe and effective staffing

Score: 3

Salisbury Renal Unit maintained safe staffing levels and had effective arrangements to respond to short-term staffing pressures. Staff told us the unit aimed to maintain a nurse-to-patient ratio of 1:4 on every shift and did not start dialysis treatment until safe staffing levels were established. Managers explained that when staff reported sick, they reviewed staffing levels and arranged additional support when required. The service used a pool of regular bank staff and could also draw on staff from other nearby dialysis services under the same provider. During the assessment, one registered nurse was absent due to sickness. The unit responded by using the clinical lead in a clinical role to support the team. Staff for the day consisted of 3 registered nurses and 1 healthcare assistant for the morning and afternoon shifts, with 2 registered nurses rostered for the twilight shift. Staff described being able to increase staffing further if patient dependency increased, for example when several patients required hoist transfers. Bank staff used by the service were renal trained, received a supernumerary period and were familiar with the service before working independently.

The unit had a stable workforce and sufficient staffing numbers to meet patients’ needs. Workforce data showed there were no open vacancies at the time of reporting. The service had an establishment of 13 whole time equivalent staff, recruited 2 new starters and had 1 leaver during the previous 12 months, resulting in a turnover rate of 7.9%. Staff told us they felt there were enough staff available to provide care and described the unit as being overstaffed at times. The unit’s staffing establishment included a registered manager, deputy manager, senior registered nurses, healthcare assistants and a dialysis assistant. The service supported up to 12 patients per session.

Leaders monitored workforce risks and responded to changes in staff availability. Sickness absences remained relatively low for most reporting periods, ranging from 1.5% to 2.7% of contracted hours. However, this increased to 6.9% and 11.3% in the 2 most recent reporting periods. Staff told us they had experienced a period when 2 staff members were absent through sickness and 2 were on annual leave. Despite this, they reported they were generally able to maintain safe staffing levels by using the bank pool and flexing resources across services.

Staff received training, supervision and opportunities for professional development. Mandatory training compliance was 95%. Staff received renal-specific competency training, and managers told us all newly appointed staff completed a supernumerary period. The service provided ongoing learning opportunities and supported staff to undertake further education. For example, one member of staff described completing an advanced renal course and undertaking a prescribing qualification, with managerial support to adjust working patterns to facilitate attendance. The service operated a formal performance management process that included objective setting, mid-year reviews, self-assessments and manager assessments. Appraisal records showed staff had completed annual performance reviews, with most staff receiving higher overall performance ratings. Staff reported receiving appraisals twice yearly.

The service carried out recruitment and employment checks. Records show Disclosure and Barring Service (DBS) checks had been completed for 3 staff members reviewed during the assessment. This helped to provide assurance staff were suitable to work in healthcare settings and contributed to patient safety. 

Infection prevention and control

Score: 3

The service had systems and processes to prevent and control infection. Staff followed infection prevention and control (IPC) procedures during treatment sessions and demonstrated a good understanding of IPC risks. We observed staff wearing personal protective equipment (PPE), including gloves, aprons, masks, and visors. Hand sanitiser was available at each dialysis station, PPE was stocked throughout the unit, and posters promoting the '5 Moments for Hand Hygiene', bare below the elbows, and PPE donning and doffing were displayed in clinical areas and staff rooms. Staff were observed washing their hands, using hand sanitiser, cleaning equipment between patients, and wiping down clinical trolleys. This reduced the risk of cross infection and supported safe patient care.

The unit was generally clean and well maintained. Environmental audits completed in June, July, and August 2026 found dialysis chairs, machines, tables, mattresses, pillows, trolleys, and waste bins were clean and in good condition. Sterile products were stored and sampled items were within their expiry dates. We observed a clean and tidy sluice area, visibly clean wheelchairs, handwashing sinks, and ‘"I am clean’" stickers on equipment. The service also used individual storage boxes for patients' tape, labelled with patient initials, which reduced the risk of cross contamination. Patients were generally allocated the same dialysis station and machine where possible, which would support tracking and outbreak management if infection concerns arose.

The service had arrangements to manage patients with known or suspected infections. An isolation room with a separate entrance and dedicated toilet was available, allowing patients to be treated without passing through the main dialysis area. Staff told us patients with infections would normally receive dialysis at the end of the treatment day to reduce the risk of transmission. Patients returning from travel to higher-risk countries were isolated for 3 months and used a dedicated dialysis machine in line with local policy. Staff also completed regular surveillance screening, including 3 monthly viral blood tests for hepatitis B and hepatitis C and monthly MRSA screening. These measures supported the early identification and management of infection risks.

The service monitored hand hygiene compliance through regular audits. We reviewed audits completed in August 2026 which showed compliance rates of 90%, 100%, and 100%. Staff generally complied with the WHO '5 Moments for Hand Hygiene', and audits confirmed appropriate PPE use, clean equipment, and good infection prevention practices. One audit identified 2 missed hand hygiene opportunities, but subsequent audits demonstrated full compliance. This provided assurance staff understood and followed hand hygiene requirements.

The service monitored infection incidents and investigated concerns when they occurred. Between March and August 2026, the unit reported one vascular access infection. The incident was assessed as having a minor impact, involved no systemic infection, and resulted in no serious harm. This suggested vascular access infections were uncommon within the service during the period reviewed.

Clinical equipment and treatment areas were generally clean. Environmental cleaning audits identified some opportunities to improve consistency in cleaning standards across the unit, particularly in relation to high-level dusting, floor corners and waiting area floors. While some areas did not consistently achieve the provider's expected standards and cleaning compliance remained below the 95% target between May and August 2026, the provider had recognised these issues and was actively monitoring the performance of the cleaning contractor. These findings primarily related to environmental cleanliness and did not indicate concerns regarding the decontamination of clinical equipment.

Medicines optimisation

Score: 3

The service managed medicines safely and had systems to support the safe storage, prescribing, administration and monitoring of medicines. Staff followed the trust's Medicines Management Policy, which provided guidance on prescribing, storage, administration, disposal and staff responsibilities. This helped ensure medicines were managed safely, consistently and in line with legal and patient safety requirements.

We observed a medicine round and saw staff administer medicines safely and in line with policy. Two registered nurses wore red ‘do not disturb’ tabards while undertaking the round to reduce interruptions. Staff transported medicines on a clinical trolley, checked patient identity and allergies before administration, and completed clinical observations, including blood pressure and temperature, where required. Staff spoke with patients about the medicines they were receiving. This reduced the risk of medicines errors and helped patients understand their treatment.

The service stored medicines securely and monitored medicine storage conditions. The medicines room was located within a secure corridor that required key fob access. Although the fire door to the medicines room was open and the medicines fridge was unlocked at the time of the inspection, patients could not access the area and there was no immediate risk to patient safety. The medicines fridge temperature was 5°C and within the required range. Records showed 2 temperature checks were missing from the August 2026 fridge temperature log; however, all other entries had been completed and were within acceptable limits. The room temperature monitoring system showed temperatures were within range. This provided assurance medicines were stored under suitable conditions to maintain their effectiveness.

Staff managed stock and maintained oversight of medicine expiry dates. We checked a sample of medicines stored in the fridge and cupboards and found all were in date. For medicines that required use within 8 weeks of opening, staff recorded the expiry date on the label, and all sampled medicines remained within the required timeframe. This reduced the risk of patients receiving expired medicines and supported safe medicines management.